SUPPORT

Installation Examples

Schweigen's Complete Ventilation System

Illustration of house
All images here are for illustrative purposes only. Please refer to user manual for specific instructions.

How to install a Schweigen Silent Rangehood

All Schweigen silent rangehoods come with Schweigen SteelFlex™ high performance safety ducting at no extra cost.

Good design practice would always see a fire-rated ducting system extend to the house exterior, rather than to the ceiling cavity. When a rangehood is ducted only into the ceiling space, the collection of humidity and grease can present very real health issues and fire hazards. Over time, the back pressure will also impact the longevity and performance of the rangehood motor.

Different Australian states have varying legislative requirements for the installation of rangehood ducting. Some will insist on ducting being vented externally (i.e. not in to the ceiling cavity); others will not. It is imperative that you check with your state building authority and/or private certifier to confirm their position.

Motor Installation Overview

Isodrive Diagram and step by step instructions
Illustration of schweigen steelflex ducting
All images here are for illustration purposes only. Please refer to user manual for specific instructions.

Motor Installation Examples

Installation example

Example of a Dektite® Roof Installation on a tiled and corrugated roof. Please refer to the Isodrive Manuals for installation procedure.

Installation example

Close up example of a Dektite® Roof Installation on a corrugated roof. For a list of experienced installers, please click here.

Installation example

Example of a Dektite Roof Installation on a tiled roof. Please refer to the Isodrive Manuals for installation procedure.

Installation example

Example of twin IsoDrive motors (SP2.3000) roof-mounted.

Installation example

Roof-mounted installation for a double storey house.

Installation example

Installation for double storey house with poly pipe covering the flexi ducting. This method was chosen to meet minimum distance requirements. Please note, the 200mm fire retardant (210mm outside dimensions) flexi duct runs inside the poly pipe, the use of flexi ducting is a must to neutralize air noise keeping the sound to a minimum.

Installation example

Installation for double storey house with custom made removable COLORBOND® shield covering the flexi ducting.

This method was chosen to meet minimum distance requirements. Please note, the 200mm fire retardant (210mm outside dimensions) flexi duct runs inside the COLORBOND® shield, the use of flexi ducting is a must to neutralize air noise keeping the sound to a minimum.







Installation for another property with the ducting run horizontally alongside the side of the house within custom made removable COLORBOND® shield.

This may sometimes be preferable to ensure the optimum length of ducting to the motor can be run.

Installation example

External motors can be installed on the wall.






Installation example on a wall

Installation examples for side mounted motors on the wall.

This method was chosen for a double story house to meet minimum distance requirements.

Please note that the 200mm fire retardant (210mm outside dimensions) flexi duct runs inside the poly pipe.

The use of flexi ducting is a must to neutralise air noise, keeping the sound to a minimum.




Another one featuring the SE.3200 motor side neatly mounted to the wall.

Kindly note that wall installations of SP.1600 motors require the additional purchase of Wall Hanging Brackets from the Spare Parts Store.

Where to Buy

Find a Store

Find a Schweigen Home Appliance stockist near you.

Find Nearest
Arrow Right